Customization: | Available |
---|---|
Application: | Variable Speed Drive |
Output Type: | Triple |
Still deciding? Get samples of US$ 118/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Inverter Model | Power (kW) G/P |
Current (A) |
Dimension (mm) | Figure | |||||
H | H1 | W | W1 | D | d | ||||
ZVF300-G0R4S2MD | 0.4 | 2.4 | 185 | 175 | 118 | 108 | 170 | Ф4 | Fig.1 |
ZVF300-G0R7S2MD | 0.75 | 7.5 | |||||||
ZVF300-G1R5S2MD | 1.5 | 7.0 | 185 | 175 | 118 | 108 | 190 | Ф4 | |
ZVF300-G2R2S2MD | 2.2 | 10 | |||||||
ZVF300-G3R7S2SD | 3.7 | 16 | 215 | 205 | 145 | 135 | 193 | Ф4 | |
ZVF300-G0R7T4MD | 0.75 | 2.5 | 185 | 175 | 118 | 108 | 170 | Ф4 | Fig.1 |
ZVF300-G1R5T4MD | 1.5 | 3.7 | |||||||
ZVF300-G2R2T4MD | 2.2 | 5.0 | |||||||
ZVF300-G3R7/P5R5T4MD | 3.7/5.5 | 9.0/13 | 215 | 205 | 145 | 135 | 193 | Ф4 | |
ZVF300-G5R5/P7R5T4MD | 5.5/7.5 | 13/17 | |||||||
ZVF300-G7R5/P011T4MD | 7.5/11 | 17/25 | 265 | 253 | 185 | 174 | 215 | Ф5.5 | |
ZVF300-G011/P015T4MD | 11/15 | 25/33 |
Item | Item Description | |
Input | Rated voltage& Frequency | Single /Three phase 220VAC . Three phase 380V.50Hz/60Hz |
Allowable Voltage range | Voltage fluctuate range:-20%~+20% Voltage unbalance rate:<3%;Frequency fluctuation:≤5% |
|
Output | Rated voltage | three phase 0~ input AC voltage |
Frequency | 0.00~600.00Hz | |
Overload capacity | Type G:150% 1minute,180% 1 second,200% transient protection Type P:120% 1minute,150% 1 second,180% transient protection |
|
Control Function | Modulation mode | Optimal space voltage vector PWM modulation |
Control mode | Sensorless vector control (SVC), V/F control . Torque control |
|
Frequency accuracy |
Digital setting::Max. Frequency×±0.01% Analog setting:Max. Frequency×±0.2% |
|
Frequency resolution | Digital setting :0.01HZ; Analog setting :Max. Frequency x0.1%. |
|
Starting frequency | 0.00~10.00Hz | |
Torque lift | Automatic torque lift: To lift the torque automatically according to the output current. Manual torque lift, Range: 0.1_30.0% |
|
Slip compensation | Setting range:0~150%,The inverter output frequency can be auto-regulated within this range according to the motor load, so as to reduce the speed variation of the motor due to load fluctuation. | |
Acceleration/deceleration time |
Minutes/Seconds can be selected as time unit .0.1~3600 can be set in sequence . | |
Carrier frequency | 1.0~15.0KHz | |
Jog function | Jog frequency range:0.01~600.00Hz, Jog acceleration /deceleration time 0.1~3600.0 can be set. |
|
V/F curve | 1:linear curve;2:quadratic;3:user defined V/F curve |