Customization: | Available |
---|---|
Application: | Three Phase Transducer |
Output Type: | Triple |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
CHZIRI ZJR2 series soft starter can work with three-phase, AC squirrel cage induction asynchronous motor, The voltage is 320V~460V, 50Hz/60Hz and the current is 1200A and below. The soft starter is a device type. It's necessary to add breakers (short-circuit protection ) and AC contactor (Bypass) inside the cabinet. Together with switches are made up of electric motor control circuit.
ZJR2 device type can work without three-phase AC motor in the process of starting too big acceleration torque, and power supply system plays a protection from excessive current harvest dynamic impact role, has the following characteristics:
1. 16 SCM control, intelligent all-digital display;
2. Can be put into practice a soft starter control multiple motors;
3. Starting modes: Current limiting starter, Voltage ramp start, Kick start +current-limiting start, kick start +voltage ramp start. Current ramp start. Voltage current-limiting double closed-loop start.
4. Free stop and soft stop, The stop time from 0 to 60 seconds can be arbitrary choosed.
5. Over current, Overload, Open phase, instantaneous stop and other fault protection.
with the flow, over loading, lack phase, instantaneous stop, and other malfunction protection;
6. Easy installation, simple operation, strong function and reasonable prices;
Item | Item Description | ||
Input Power Supply | Input Voltage | Three Phase 380V-15% ~ 415+10% | |
Frequency | 50/60Hz | ||
Adaptive Motor | Squirrel-cage three-phase asynchronous motor | ||
Starting Times | It is recommended not to exceed 20 times per hour. | ||
Control Mode | 1) Operation panel control; 2) Operation panel + external control; 3) External control; 4) External control + COM control; 5) Operation panel + external + COM control; 6) Operation panel + COM control; 7) COM control; 8) No start or stop operation. | ||
Start Mode | 1) Current-limiting start; 2) Voltage ramp start; 3) Kick start + current-limiting start; 4) Kick start + voltage ramp start; 5) Current ramp start; 6) Voltage current-limiting double closed-loop start. | ||
Stop Mode | 1) Soft stop; 2) Free stop. | ||
Protective Function | 1) Open loop protection for external instantaneous stop terminals; 2) Over-heat protection for soft starter; 3) Protection for too long starting time; 4) Input open phase protection; 5) Output open phase protection; 6) Unbalanced three-phase protection; 7) starting over current protection; 8) Running overload protection; 9) Under voltage protection for power voltage; 10) Over voltage protection for power voltage; 11) Protection for fault parameter setting; 12) Load short circuit protection; 13) Auto restart or incorrect wiring protection; 14) Incorrect wiring protection of external control stop terminals. | ||
Ambient | Place to be used | Indoor location with good ventilation free from corrosive gas and conductive dust. | |
Altitude | Below 3000M. It have to rise the rate power when the altitude is more than 3000M. | ||
Ambient Temperature |
-30~+55ºC |
||
Ambient Humidity | ≤90%RH without dew condensation. | ||
Vibration | <0.5G | ||
Structure | Protection Class | IP20 | |
Cooling Pattern | Natural wind cooling. | ||
Model | Rated Power(KW) | Rated Current (A) | Outline Size | Install Size | Net Weight (KG) |
||||
H1 | W1 | D | H2 | W2 | d | ||||
ZJR2-3055 | 5.5 | 11 | 270 | 145 | 159 | 245 | 130 | M6 | < 3.5 |
ZJR2-3075 | 7.5 | 15 | 270 | 145 | 159 | 245 | 130 | M6 | < 3.5 |
ZJR2-3110 | 11 | 22 | 270 | 145 | 159 | 245 | 130 | M6 | < 3.5 |
ZJR2-3150 | 15 | 30 | 270 | 145 | 159 | 245 | 130 | M6 | < 3.5 |
ZJR2-3185 | 18.5 | 37 | 270 | 145 | 159 | 245 | 130 | M6 | < 3.5 |
ZJR2-3220 | 22 | 44 | 270 | 145 | 159 | 245 | 130 | M6 | < 3.5 |
ZJR1-3300 | 30 | 60 | 270 | 145 | 159 | 245 | 130 | M6 | < 3.5 |
ZJR1-3370 | 37 | 75 | 270 | 145 | 159 | 245 | 130 | M6 | < 3.5 |
ZJR1-Z3450 | 45 | 90 | 270 | 145 | 159 | 245 | 130 | M6 | < 3.5 |
ZJR1-Z3550 | 55 | 110 | 270 | 145 | 159 | 245 | 130 | M6 | < 3.5 |
Model | Power (KW) | Current (A) | Outline Size | Install Size | Packing Size(mm) | Gross Weight | ||||
H1 | W1 | D | H2 | W2 | d | (KG) | ||||
ZJR2-3055/4055 | 5.5 | 11 | 270 | 145 | 159 | 245 | 130 | M6 | 670*400*245mm/4PCS | 18KG |
ZJR2-3075/4075 | 7.5 | 15 | 270 | 145 | 159 | 245 | 130 | M6 | ||
ZJR2-3110/4110 | 11 | 22 | 270 | 145 | 159 | 245 | 130 | M6 | ||
ZJR2-3150/4150 | 15 | 30 | 270 | 145 | 159 | 245 | 130 | M6 | ||
ZJR2-3185/4185 | 18.5 | 37 | 270 | 145 | 159 | 245 | 130 | M6 | ||
ZJR2-3220/4220 | 22 | 44 | 270 | 145 | 159 | 245 | 130 | M6 | ||
ZJR2-3300/4300 | 30 | 60 | 270 | 145 | 159 | 245 | 130 | M6 | ||
ZJR2-3370/4370 | 37 | 75 | 270 | 145 | 159 | 245 | 130 | M6 | ||
ZJR2-3450/4450 | 45 | 90 | 270 | 145 | 159 | 245 | 130 | M6 | ||
ZJR2-Z3550/4450 | 55 | 110 | 270 | 145 | 159 | 245 | 130 | M6 |
Scope of application:
ZJR2 series soft starter motor applies to centrifuges, blower, compressor, transport planes, mixer, rolling ball mill broken machines and mechanical equipment motor starter.CHZIRI Clients